Fire Detection System |
|||||||||||||
It uses multi-spectral Wide Band IR™ (1.2 - 3.5 micron bandwidth), Near Band IR™ (.7 to 1.1 micron bandwidth), and Visible Band (0.4 - 3.5 micron bandwidth) to see all fire types. The Wide Band IR allows the detector to see through acetone, smoke, chemical gasses and vapors. Unique Two-Stage Fire Detection ResponseThe ALERT First Stage response initiates audible and visible signals, notifying the operator of an existing fire of 4kW or more. If the fire does not self-extinguish, the Second Stage ALARM activates and signals for immediate suppression release once the fire exceeds a threshold of 13 kW (the equivalent of an 8"(203 mm)-diameter polypropylene pool fire).Each fire detector has an exceptionally wide, 120° field of view to provide optimal coverage of the fire-threat area. Detectors should be installed in adequate numbers and positions to ensure that any possible fire is in the field of view of at least one fire detector, unobstructed by plastic partitions. Note: Fire suppression equipment must be ordered separately. Call to discuss your application. See application illustration for suggested configuration. Part numbers below include installation in specified Terra wet processing station. |