Product Details
- Available Certified ISO Grade Designs: ISO 7, ISO 8
- Terra's ValuLine static dissipative PVC paneled cleanrooms feature the same cleanliness, strength and durability of powder-coated steel frames, the same stainless steel wall trim and modularity as Terra's Standard cleanrooms. ValuLine rooms reduce costs with simple on-off power supply units and without the top trim and power status indicators on Standard line rooms. SDPVC reduced static cling and reduces particle counts.
- www.planner5d.com/b2b/terra/v/?key=f3a9f7cbb4792b757f8e6cea031dc0dc&viewMode=3d
- COMPONENTS INCLUDED:
- Steel frame – posts and beams of 2" (51 mm) square tubing, powder coated
- Steel ceiling grid – joists and cross members 3" (76 mm) T-bars
- Static-dissipative PVC wall and door panels
- ACCESSORIES INCLUDED:
- (1) Door, cleanroom with door closer – 36" x 81", powder-coated aluminum door frame, SDPVC panel, UL leak-rated (6710-15A-L-PC)
- (1) LED Light Module – 4000 lumens, 5 color temps, 40 W, 120-277 VAC (3800-41C-VL)
- (3) Power Supply Units – Switched supply to six FFU/light receptacles, 20W 120 VAC (6600-20B-VL)
- Ceiling Panels -- 2' x 4', white polypropylene as required to fill ceiling grid
- OPTIONAL ACCESSORIES DISPLAYED ON MODEL:
- HEPA Fan/Filter Units to meet desired ISO cleanliness rating (ISO 7-8 shown on model)*
- Control boxes with air pressure gauge, etc.*
- Top trim with power status indicator indicators*
- * These items are shown on 3D model, but are not included in base price
- All electrical components are UL and UL-C listed
- Electrical system UL Listing Declaration available (order separately), to help meet permit requirements
- Rooms ship disassembled with assembly instructions. Two assemblers make the process easier
- FFUs and lights plug into Power Supply Units. Power Supply Units plug into US wall receptacles. Each PSU provides ceiling power and a non-switched GFI outlet on a wall post and requires a dedicated 20 A circuit.
- FFUs add 13" (330 mm) overhead to height. Additional 9" to 11" (230 to 280 mm) clearance is required for air flow and installation. Total clearance required above filter face is 22" to 24" (560 to 610 mm)
- Ships palletized to fit through 36" doorway. Forklift, lift gate and pallet jacks may be required
- Terra assumes no responsibility for meeting local building regulations, including fire and seismic codes
- Check your local planning department for regulations applying to your installation
Specs
• Frame Material: Powder-Coated Steel
• Height: 8'
• Depth: 8'
• Width: 12'
• Panel Material: Static-Dissipative PVC
• Unit of Measure: EA
• Marks & Listings: UL, ULC
• Electrical Specifications: 120 V, 18 A, 2,160 W, 50/60 Hz
• Dimensions, Product: 148" W x 99" D x 96" H
• Weight, Shipping: 2,000 lb
• Dimensions, Shipping: 153" W x 62" D x 38" H
• Package Type: Skid